How energy sub-metering works in commercial property and industry

By the Vera Automation engineering team · Updated

Short answer

Energy sub-metering is the installation of additional electricity meters downstream of the main utility meter — on each tenant, floor, department, production line or large machine — so that consumption can be measured and allocated separately. The sub-meters are read automatically, usually over Modbus, into a central system that produces tenant recovery figures, cost allocations and consumption reports, and flags abnormal usage.

Why sub-meter?

  • Tenant recovery — landlords recover electricity costs from tenants on measured, not estimated, consumption.
  • Cost allocation — manufacturers and campuses assign energy cost to the department, line or product that used it.
  • Finding waste — after-hours loads, equipment left running and faulty systems become visible.
  • Verifying projects — solar, LED retrofits and HVAC upgrades can be measured before and after.

How the meters are installed

Sub-meters are installed in distribution boards on the circuits to be measured. Smaller loads use direct-connected meters, where the supply passes through the meter. Larger loads use CT-operated meters, where current transformers clipped around the conductors let the meter measure high currents safely. Installation must be done by a qualified electrician, and CT ratios and orientation must be recorded and checked — a reversed CT is one of the most common causes of wrong readings.

How the meters are read

Modern sub-meters provide a Modbus RTU (RS-485) or Modbus TCP interface, or a pulse output for older designs. A gateway reads all meters in the building at regular intervals, stores interval consumption and sends it to a central platform. This replaces monthly manual readings, which are slow, error-prone and give no insight into when energy was used. See how to connect a Modbus meter to the cloud.

From readings to recoveries

  1. Collect interval readings (commonly 30-minute) for every meter.
  2. Validate: fill or flag gaps, detect counter resets and meter swaps, compare the sum of sub-meters with the main meter.
  3. Apply the tariff structure — including time-of-use rates and demand where relevant — and allocate common-area consumption according to the lease.
  4. Produce tenant statements and management reports, and export to the billing or property system.

What to check before you start

  • Which questions you need answered — this determines where meters go.
  • Existing meters: many have communication ports that were never connected.
  • Meter accuracy class and suitability for billing, and whether the lease or local regulations set requirements.
  • Communications routes between distribution boards and the gateway.
  • Who will receive and act on the reports.

See our energy monitoring service and property & facilities work.

FAQ

Frequently asked questions

Can existing prepaid or tenant meters be read automatically?

Some can, if they have a communications port or pulse output. Others need replacing or supplementing with communicating meters. A site survey answers this quickly.

How accurate does a sub-meter need to be?

For billing tenants, use meters of an appropriate accuracy class installed and verified correctly; check your lease terms and local requirements. For internal allocation, the requirement is usually less strict.

Can water be sub-metered in the same system?

Yes. Water meters with pulse or Modbus outputs can be read by the same gateway and reported alongside electricity.